MYP mine mobile shielding rubber sheathed flexible cable
The insulation resistance between cable insulated main line cores and between main line core and ground wire shall not be less than 100MΩ · km when converted to 20 ℃. The transition resistance of the shielding layer of the main line core shall not be higher than 3kΩ when converted to 20 ℃. The MYP cable consists of three main cores with insulation shielding and a ground wire covered with a semi-conductive rubber layer, which are twisted around the semi-conductive rubber layer cushion core to form a cable. Extruded black chlorinated polyethylene rubber sheath or black neoprene rubber sheath.
Classification:
Key words:
- Product Description
-
MYP mine mobile shielding rubber sheathed flexible cable
Flexible shielding rubber-sheathed cables for mining purposes
Model (Type):MYP Rated voltage (Rating Voltage):380/660VCore Number Section
Name. cross seconal areas mm2
conductor structure
Conductor structure NO./mm
Insulation thickness
Insulation thickness mm
Sheath thickness
Sheath thickness mm
Cable outer diameter
Average diameter
Reference Weight
Cable approx.
weight
kg/km
Maximum DC resistance of conductor (copper)
Max.D.C.
Resistance(20 ;
Carrying capacity at 20 ℃
Current carring capacity(20 ℃ )
A
Nominal
Normianal mm
Max.
Max
mm
3 × 4 1 × 4
56/0.30
1.4
3.5
22.9
25.2
730
4.950
35
56/0.30
4.950
3 × 6 1 × 6
84/0.30
1.4
3.5
24.7
27.2
959
3.300
46
84/0.30
3.300
3 × 10 1 × 10
84/0.40
1.6
4.0
29.7
32.7
1427
1.910
64
84/0.40
1.910
3 × 16 1 × 10
126/0.40
1.6
4.0
32.2
35.4
1675
1.210
85
84/0.40
1.910
3 × 25 1 × 16
196/0.40
1.8
4.5
38.3
41.0
2419
0.780
113
126/0.40
1.210
3 × 35 1 × 16
276/0.40
1.8
4.5
42.4
46.6
2952
0.554
138
126/0.40
1.210
3 × 50 1 × 16
396/0.40
2.0
5.0
47.4
51.0
3741
0.386
173
126/0.40
1.210
3 × 70 1 × 25
360/0.50
2.0
5.0
52.4
57.1
4790
0.272
215
196/0.40
0.780
Remarks:
1. The insulation resistance between cable insulated main line cores and between main line cores and ground wires shall not be less than 100MΩ · km when converted to 20 ℃.
2. The transition resistance of the main core shielding layer shall not be higher than 3kΩ when converted to 20 ℃.
3. Product standard: MT818.5-1999.
4. MYP cable consists of three main cores with insulation shielding and a ground wire covered with semi-conductive rubber layer, which are twisted around the semi-conductive rubber layer cushion core to form a cable. Extruded black chlorinated polyethylene rubber sheath or black neoprene rubber sheath.
5. Conductive core: soft copper wire, its performance conforms to GB/T3956-1997.
6, insulation: the use of GB7594.2-1987 XJ-00A type rubber.
7. Line core identification: insulation color separation identification is adopted, and the main line core is red, green and white.
8. Ground wire: covered with semi-conductive rubber.
9, insulation shielding: in the insulation table bread semi-conductive belt.
10. Cable formation: 3 main lines and 1 ground wire are twisted around the semi-conductive rubber pad core to form a cable in the right direction.
11. Sheath: GB7594.7-1987 XH-03A type rubber is adopted. The oxygen index of the sheath rubber shall be ≥ 40.
12. The flame retardant performance of the finished cable meets the requirements of the MT386-1995.
13. Cable mark: model, voltage, specification and manufacturer's name are printed on the surface of the cable.